Commercial Chiller Installation: Power, Plumbing and Space

SYSTEM SETUP · COMMERCIAL · 1/2 TO 3 HP

  • 230 V1 to 3 HP models
  • 115 Vor 230 V on 1/2 HP
  • 5 ftclear in front
  • ±1°Fcontroller band

Commercial Arctica chillers cool fish store systems, seafood and lobster holding tanks, aquaculture racks, school labs, ponds and large display aquariums. They work like the home models, with bigger plumbing, a dedicated electrical circuit and more air space. Plan the room, the power and the water loop before the chiller arrives. Setting up a home aquarium? See residential chiller installation.

Plan the room Power Plumbing Several tanks Commissioning Upkeep Questions

Which chiller and which voltage

ModelSizePowerWater ports (manual)
DA-500 / DA-500-230V1/2 HP115 V or 230 V1"
DA-10001 HP230 V1"
DA-15001-1/2 HP230 V1"
DA-20002 HP230 V1-1/4"
DA-30003 HP230 V1-1/4"

Not sure of the size? The chiller sizing calculator has a setting for plunge tubs and counts room heat, lights and pumps. For a large system, text us the total gallons and the room temperature.

1. Plan the room

Clearance around a commercial chiller, seen from aboveJBJ's commercial manual asks for 8 inches behind the unit, 4 feet on each side and nothing within 5 feet of the front.back wallChillertop view, level floor8 in4 ft4 ft5 ft clear in frontno stacking, no slope, air free to move
  • Space: the JBJ commercial manual asks for 8 inches behind the unit, 4 feet on each side and nothing within 5 feet of the front, where the hot air leaves.
  • Level and alone: set it on a flat, level base. Never stack it on other equipment or tilt it.
  • Air temperature: the manual lists 70 to 104°F room air and humidity under 80%. Do not run it outdoors below 50°F.
  • The heat has to go somewhere. A 1 HP chiller blows a lot of warm air. In a small equipment room, plan a vent or exhaust fan so the room does not heat up and slow the chiller down.
  • Water and drains: keep it where a leak or a spill runs to a floor drain, not into the electrics.

2. Power

Use a licensed electrician. Commercial chillers draw much more current than home units. Wire size and breaker size per model are in the table on page 9 of the JBJ commercial manual.

  • Give the chiller its own circuit with its own breaker and earth-leakage protection. Do not share it with the pump or the air pump. The breakers are not included with the chiller.
  • Check the label voltage against the outlet before you plug in. A 230 V chiller needs a 230 V circuit.
  • Ground it properly. The manual says never to a gas pipe, a water pipe or a phone line.
  • Run every cord with a drip loop so water cannot reach the plug.

3. Plumbing

  1. Water goes in low and out high. The pump feeds the lower IN port; the upper OUT port sends cooled water back to the tank. Swapping them lowers cooling.
  2. Pull from the sump or filter tank, after the mechanical filter or a strainer, so debris and slime stay out of the titanium coil.
  3. Give it plenty of flow. The manual says to use a large pump and never run the chiller without water moving. Size the pump for the real height and pipe run, not the box rating.
  4. Use rigid PVC in the 1" or 1-1/4" size of the ports, with a union on each side so the chiller can come out for service, and a ball valve to set the flow.
  5. Add a bypass (a tee and a valve back to the sump) when your pump moves more water than you want through the chiller.
  6. Leak-test with the power off. Run water through the whole loop and check every joint before the chiller gets power.

4. One chiller, several tanks

One commercial chiller cooling several tanksSeveral tanks drain into one sump. A pump sends the water through a strainer or filter and then into the chiller's lower IN port. Cooled water leaves the upper OUT port into a manifold with a valve for each tank.Tank 1Tank 2Tank 3Sump / reservoirPUMPstrainer /filter58.0CommercialchillerIN (low)OUT (high)manifold, one valve per tank

Fish stores and aquaculture systems often run one central chiller for a row of tanks. The tanks drain to a shared sump; one pump sends the water through the filter and chiller; a manifold with a valve per tank returns it.

  • Size the chiller for the total water in the loop, tanks plus sump plus pipes.
  • Balance the return valves so every tank gets cold water and none overflows.
  • Use check valves or siphon breaks on the returns so a power cut does not drain the tanks into the sump.
  • Make sure the sump can hold the water that drains back when the pump stops.

5. Commissioning

  1. Pump on, water through the chiller, no leaks.
  2. Power on at the breaker. The display shows the water temperature.
  3. The compressor starts after a 3-minute delay. That protects it and is normal.
  4. Set the temperature: hold UP for about 3 seconds, then use UP or DOWN. The setting saves itself after 10 seconds.
  5. The controller holds the water within about 1°F of your setting, switching on and off on its own.
  6. Check the reading against a good thermometer and watch the first day: water temperature, pump flow, room temperature.

6. Upkeep

  • Clean the condenser fins and grille once a month in a commercial room; dust is the number one cause of lost cooling.
  • Keep the pre-filter or strainer clean so flow stays up.
  • Flush the heat exchanger with fresh water when cooling drops. The care guide shows how.
  • Keep spare wear parts on hand: probes, gaskets, compression sockets and a controller. Find the right ones in the parts checker.

Questions

Can one chiller cool several tanks?

Yes, when the tanks share one sump and a manifold returns the water. Size the chiller for all the water in the loop and balance the return valves.

Do I need an electrician?

For the 230 V models, yes. They need their own circuit and breaker sized from the manual's table. The 1/2 HP 115 V model plugs into a standard outlet, ideally on its own circuit.

Why titanium?

Salt water eats copper. The titanium coil in every Arctica chiller handles salt water, brackish water and seafood systems.

Can it cool a cold plunge or a pond?

Many people use Arctica chillers for plunge tubs and ponds. Pick plunge mode in the calculator, which adds extra margin, and keep the chiller under cover and out of the rain.

Can it go outside or in a garage?

Only under cover, dry and within the 70 to 104°F air range in the manual, never below 50°F.

What happens after a power cut?

Check the display when power comes back: the water temperature and your setting. Check valves on the returns keep the tanks from draining into the sump while the pump is off.

PVC or flexible hose?

Rigid PVC for long runs and permanent installs; a short piece of reinforced hose near the chiller can soak up vibration. Use unions so the chiller lifts out.

Planning a big system? Text a photo of the room and the tanks to 916-800-2653 or email us the gallons, room temperature and the water temperature you need. We also set up wholesale accounts for stores and schools. Manual: JBJ Arctica commercial chillers.